FuelPure Canada Ltd. has twenty-five (25) years of experience providing fuel purification and tank cleaning services for a variety of government,
institutional, and corporate applications in Canada. FuelPure filtration equipment and filter elements are aviation quality, for the highest absolute
filtration effectiveness.
Through the Technical Standards & Safety Authority, FuelPure Canada Ltd. is registered under the Gasoline Handling Act and subject to the regulations and limitations
thereof with the Fuels Safety Branch as a Contractor (registration number FS R0076456375).
The Ministry of the Environment and Energy has granted FuelPure Canada Ltd. a “Certificate of Approval” as a Registered Waste Management System
(Registration Number A821178) under the Environmental Protection Act. Generated wastes are batched, manifested, and disposed of to a licensed recycling facility.
FuelPure Canada Ltd. vehicles are approved as a waste management systems (WMS) to receive, transport, and transfer waste under the Environmental Protection Act.
All driver’s carry certification verifying successful completion of a training and safety program in Hazardous Materials Handling.
FuelPure Canada Ltd. maintains Comprehensive General Liability Insurance, Commercial Automobile Liability Insurance, and Environmental Impairment Liability
Insurance of $5,000,000 each.
FuelPure Canada Ltd. maintains Workers Compensation Coverage. A Clearance Certificate from the Workplace Safety & Insurance Board is available throughout
the contract period upon request.
FuelPure Canada Ltd. has commenced an ISO 14001 Implementation Project with the assistance of KPMG and DPI Environmental.
FuelPure Process / Services

A FuelPure Technician will sample the tank to be cleaned and custom the filtration process with any combination of filters and micron ratings:
Cyclone: The cyclonic action draws the heavier waste material to the bottom to be removed, fuel then passes through the top of the unit to the filter vessels.
• Pleated Media Filters: Sediment Filter with micron ratings from ¼ to 75.
• Fiberglass Filters: High efficiency migration barrier guarantees that no fibres will pass downstream.
• Coalescer Filters: Particle and emulsified water removal.
• Aquacon Filters: Water absorbing cartridges remove free and absorbed water to less than 2 ppm.
The suction hose is moved throughout the tank to ensure all areas of the tank have been cleaned. The hose has a clear section that allows the operator to see the waste being drawn into the system and when areas of the tank no longer have any visible contamination. The process is continued until all contamination has been removed. A sample is then taken of the finished tank(s) to ensure removal of all contamination.
Turbo-Flush and Purification (TFP)
Removal of water, sediment and contamination from tank surfaces. Removal of suspended contamination through continued cycling until fuel reaches five (5) microns or less in purity.
Fuel Transfer (FT)
Removal of water, sediment and contamination from fuel during a transfer or pump out, once through the filtration system.
Independent Laboratory Analysis (ILA)
Available upon request at additional cost.